LKE'S air insulated LBS panels are designated LCA for L(LBS panel)-C(Cable incoming/outgoing) A(Air insulated).

If a LCA unit air load break switch, it is further designated LCA-A, and if it houses a gas load break switch it is designated LCA-G, finally if it houses a vacuum load break switch it is designated LCA-V.

LCA panels are all indoor systems which are extendable so they can be combined to build larger distribution switchboards or ring main units (RMUs).

Further more, LCA-A, LCA-G and LCA-V can be combined in series or parallel connection to build a whole switch board system. This allows for more economical solutions where smaller loads are protected by switches with lower breaking capacity whereas higher loads are protected by switches with higher breaking capacity.

LK-LCA-V panel which houses the LK-VLBS.
LCA-A, LCA-G and LCA-V can be combined.The pictures above and on the left are switchboards composed of a combination of LCA-A and LCA-V panel units. In these particular instances, LCA-A panels were deployed as incoming units whereas LCA-V units were deployed as transformer protection units.
Single LK-LCA-A panel which houses an inverted LK-LBS with fuses is also available, often used as a transformer protection unit in outdoor applications.

Panels housing LK-LBS are commonly used as incoming units or as isolator units.

The LK-LBS/fuse combination is used usually as transformer protection units for transformers of ratings less than 800 kVA.

The diagrams on the right represent some of the possible arrangements within the LCA-A.

The LK-LCA housing the LK-VLBS will protect transformers up to a rating of 5000 kVA. With the LK-VLBS, the panel must be equipped with surge arrested to protect against over-voltages.

Furthermore the LK-LCA-V panels are equipped with current protection relays for overload and short circuit protection.

The diagrams on the right represent some of the possible arrangements within the LCA-V.

LK-LCA 12/24 Load Break Switch panels
Medium Tension Metal-clad Switchgear
LCA-A 12/24 Load Break Switch panels
LCA-V 12/24 Load Break Switch panels
LCA-G 12/24 panels housing GLBS switches

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 