LH-MX SERIES MINIATURE CIRCUIT BREAKER
Normal Service Conditions
  • Ambient air temperature : no less than -5�C and no more than +40�C
  • Relative humidity : no more than 50% at +40�C
  • Altitude : no more than 2000m
  • Pollution Degree : Class 3
The LH-MX series Miniature Circuit Breaker (MCB) provide 6KA & 10KA short circuit breaking capacity with efficient and reliable control and protection of final sub-circuit and equipment against overload and short circuits in commercial and industrial power distribution systems.

The IEC/EN 60898 standard defines various tripping characteristic for MCB, they differ from one another by the response value of the short circuit release :

B characteristic units react at min. 3 to max. 5 times rated current and are used for short circuit and over current protection in high sensitivity area such as school, hospital, electronic control systems.

C characteristic units react at min. 5 to max. 10 times rated current which must not cause tripping, such as commercial and light industrial electrical distribution systems.

D characteristic units react at min. 10 to max. 20 times rated current and are used where is a high inrush current peaks occur, eg. With transformers, motors with severe starting duty or group of luminaries in the downstream.

The LH-MX series MCB has a current rating from 6A to 63A and are available in 1 to 3 pole, 1P + N or 3P + N configurations.

LH-MX10 MCB 10 kA construction LH-MX6 MCB 6 kA construction

 


 